Repaired Dining Room RTU

Near San Jacinto Blvd. Austin Texas 78701

Repaired Dining Room RTU. I found stage one and two cycling on and off on high head pressure. I clean the entire condenser coil with Viper coil cleaner. I repaired an overcharge with refrigerant and a restriction in the liquid line. As of now all four compressors are running and no further action needed at this time.

Check out the Areas We Serve and jobs we are doing by clicking: https://setpoint.services/areas-we-serve/