Cleaned and Serviced Ice Machine head system, including evaporator section and condenser coil. Diagnosed T4 fault condition and found evaporator outlet temperature (T4) sensor shorted, measuring approximately 475 ohms, indicating sensor failure. Replaced evaporator outlet temperature (T4) sensor. Verified proper sensor readings and confirmed normal system operation after replacement.