Cold Shot Chiller Cleaning
Cold Shot Chiller Cleaning. I washed out the condenser coil, charged system with 6lbs of r410a as the sight glass was flashing near system set point. I called Cold Shot Chillers tech support and adjusted system parameters as the controller and the module was not communicating quick enough causing the system to shut off after 10 seconds of pump operation. I found a couple of wires disconnected from the starter module, refastened wires. Monitored the system until thermostat satisfaction.