Haskris Chiller Repair
Haskris Chiller Repair. Inspected chiller operation and electrical components. Checked compressor electrical performance and verified compressor drawing 11.4 amps on common. Measured approximately 6 amps on each start and run conductor, indicating normal compressor load at time of inspection. Identified several loose electrical connections within the control and power wiring and secured all affected connections. Replaced compressor potential relay, compressor start capacitor, and compressor run capacitor due to condition and as a preventative measure. Verified proper start-up and operation following component replacement.