Repaired Walk In Freezer. Found both the condenser and evaporator not operating. Investigation determined the issue was electrical. Traced the breaker line and located a broken electrical connection that had previously been wrapped with blue tape. The taped section showed burn marks, indicating overheating at the connection point. The electrical connection was properly reconnected and secured.