Walk In Cooler Repair. The evaporator iced over upon arrival. I found TXV bulb was improperly mounted and defrost clock not installed on the evaporator. I Deiced the evaporator coil. Remounted the TXV bult. Installed a defrost clock to control the systems pump down function. No further action needed tonight. Box temperature dropped below 45*f before departure.